Instruction Guide – Massa M3 Wireless Sensor Evaluation Kit Page of 14
M3 Kit Guide 111017.docx 10-20-2011
7
PRELIMINARY
M3 Application Software
Validating Gateway Placement for Reliable Wireless Connectivity
The RF signal strength between the Gateway and the Sensor should be checked to ensure a reliable
communication link. Before testing for signal strength, verify that the antennas on both the Sensor
and the Gateway are vertical. As previously discussed, the M3 Software Status reports the Sensor’s
radio signal strength at the Gateway. This report has four reporting levels, “Very Strong”, “Strong”,
“Moderate”, and “Weak”, as shown in the Radio column in the figure below.
To check the signal strength, go to the “Data” tab and click on one of the “Acquire Data” buttons.
Repeat this several times to check the repeatability of the radio signal strength. If the signal strength
is “Very Strong”, there will be a very reliable communication link. However, this condition will not
always exist. A “Moderate” signal strength is acceptable, but a “Weak” signal may require
repositioning the Gateway since typically the Sensor cannot be moved as it is installed on a process
tank. If the Gateway cannot be placed close enough to the Sensor to produce a strong enough
signal, a Digi Wall Router (repeater) may be required. The Gateway can be located outdoors, since it
is rated for temperatures of -30ºC to +70ºC, but it must be placed in a watertight enclosure.